Case: T08FR00489
Case Details
Entered Date:
02/15/2008
Applicant:
CENTRO NP HOLDINGS 1 SPE LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR00489
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Address numbers shall be in accordance with Pima County address display requirements. |
02/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove the storage from obstructing the electrical service equipment located by the employee break room. |
02/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Repair or replace the water flow gong for the automatic sprinkler system located on the southwest side of the building. |
02/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.6 The portable fire extinguisher located by the main entrance shall not be obstructed or obscured. |
02/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.9 The portable fire extinguisher located by the main entrance shall be mounted so that it's top is no more than 5 ft above the floor. |
02/15/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3-2.2 Post a sign above the inside of the main entrance doors stating," THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." |
02/15/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.4 The exit sign located by the restrooms shall be illuminated during power supply failure. |
02/15/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Test and repair all emergency lighting units that do not operate during power supply failure. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00489
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |