Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR00254
Case Details
Entered Date:
01/25/2008
Applicant:
COPE BEHAVIORAL SERVICES INC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR00254
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2008 | INSP - FULL | RSPANGLE | Violation | TFC 1008.1.8 REMOVE DOUBLE DEAD BOLT LOCK FROM GATE ON PATIO. EXIT EGRESS DOORS SHALL BE READILY OPENABLE WITHOUT THE USE OF A KEY. |
01/25/2008 | INSP - FULL | RSPANGLE | Violation | TFC 1027.5 EXIT SIGN AT THE BACK DOOR NEEDS THE EMERGENCY POWER TO OPERATE. |
01/25/2008 | INSP - FULL | RSPANGLE | Violation | TFC 508.5.4 MATERIALS STORED IN THESPRINKLER SYSTEM RISER ROOM NEEDS TO BE REMOVED. |
01/25/2008 | INSP - FULL | RSPANGLE | Violation | TFC 510.1 A SIGN IS REQUIRED ON THE DOOR FOR THE AUTOMATIC SPRINKLER SYSTEM RISER TO IDENTIFY ITS LOCATION FOR FIRE PERSONNEL. |
01/25/2008 | INSP - FULL | RSPANGLE | Violation | TFC 903.5 SPRINKLER SYSTEM MUST BE INSPECTED AND TESTED ANUALLY. RECORDS MUST BE AVAILABLE ON THE PREMISES. |