FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR00254
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/25/2008 INSP - FULL RSPANGLE Violation TFC 1008.1.8 REMOVE DOUBLE DEAD BOLT LOCK FROM GATE ON PATIO. EXIT EGRESS DOORS SHALL BE READILY OPENABLE WITHOUT THE USE OF A KEY.
01/25/2008 INSP - FULL RSPANGLE Violation TFC 1027.5 EXIT SIGN AT THE BACK DOOR NEEDS THE EMERGENCY POWER TO OPERATE.
01/25/2008 INSP - FULL RSPANGLE Violation TFC 508.5.4 MATERIALS STORED IN THESPRINKLER SYSTEM RISER ROOM NEEDS TO BE REMOVED.
01/25/2008 INSP - FULL RSPANGLE Violation TFC 510.1 A SIGN IS REQUIRED ON THE DOOR FOR THE AUTOMATIC SPRINKLER SYSTEM RISER TO IDENTIFY ITS LOCATION FOR FIRE PERSONNEL.
01/25/2008 INSP - FULL RSPANGLE Violation TFC 903.5 SPRINKLER SYSTEM MUST BE INSPECTED AND TESTED ANUALLY. RECORDS MUST BE AVAILABLE ON THE PREMISES.