Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T08FR00254
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2008 | INSP - FULL | Violation | TFC 1008.1.8 REMOVE DOUBLE DEAD BOLT LOCK FROM GATE ON PATIO. EXIT EGRESS DOORS SHALL BE READILY OPENABLE WITHOUT THE USE OF A KEY. | |
01/25/2008 | INSP - FULL | Violation | TFC 1027.5 EXIT SIGN AT THE BACK DOOR NEEDS THE EMERGENCY POWER TO OPERATE. | |
01/25/2008 | INSP - FULL | Violation | TFC 903.5 SPRINKLER SYSTEM MUST BE INSPECTED AND TESTED ANUALLY. RECORDS MUST BE AVAILABLE ON THE PREMISES. | |
01/25/2008 | INSP - FULL | Violation | TFC 510.1 A SIGN IS REQUIRED ON THE DOOR FOR THE AUTOMATIC SPRINKLER SYSTEM RISER TO IDENTIFY ITS LOCATION FOR FIRE PERSONNEL. | |
01/25/2008 | INSP - FULL | Violation | TFC 508.5.4 MATERIALS STORED IN THESPRINKLER SYSTEM RISER ROOM NEEDS TO BE REMOVED. |