Case: T08FR00237
Case Details
Entered Date:
01/24/2008
Applicant:
BSH INVESTMENTS LLC
Description:
Full Inspection Intermountain Center for Human Development Property Rep: Barbra Smyth (520) 721-1887 EXT 5214
Outstanding Inspections
Case Number: T08FR00237
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2008 | INSP - FULL | JLONGO | Correction Required | Please correct the following Tucson Fire Code violations |
01/24/2008 | VIOL - FIRE SERVICE FEATURES | JLONGO | Correction Required | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____ Please remove all items blocking access to sprinkler riser |
01/24/2008 | VIOL - FIRE SERVICE FEATURES | JLONGO | Correction Required | 510.1 Identification Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____ Lable door to the building's riser room as "Riser Room" |
01/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.... fire protection systems and equipment shall be inspected, tested and maintained... ____ Test/Inspect Alarm system or show proof of completion ____ Test/Inspect Sprinkler system or show proof of completion |
01/24/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background ____ Properly lable main entrance door with above specifications ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after _2_/_7_/_08_ Call Inspector Longo at 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo |