Case: T08FR00237

Parcel: 13405116F


Addresses:

994 S HARRISON RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE SERVICE FEATURES

Case Number - T08FR00237

Inspection Description - VIOL - FIRE SERVICE FEATURES

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/24/2008 VIOL - FIRE SERVICE FEATURES Correction Required 508.5.4 Obstruction.
Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants.

_____ Please remove all items blocking access to sprinkler riser
01/24/2008 VIOL - FIRE SERVICE FEATURES Correction Required 510.1 Identification
Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air conditioning, sprinkler risers and valves, or other fire detection, suppression, or control elements shall be identified for use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.

_____ Lable door to the building's riser room as "Riser Room"