Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/22/2008

Applicant:

FURRS FAMILY DINING

Description:

Full inspection

Outstanding Inspections

Case Number: T08FR00226
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
01/23/2008 INSP - FULL JLONGO Correction Required Please correct all noted Tucson Fire Code Violations.
01/23/2008 VIOL - ADMINISTRATION JLONGO Correction Required 102.4 Application of building code. The design and construction of new structures shall comply with the International Building Code, and any alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the International Building Code, shall be made in accordance therewith. A Certificate of Occupancy shall be provided To obtain a Certificate of Occupancy or a replacement copy, contact the city of Tucson Development services Department (DSD) located at 201 N. Stone, (520) 791-5550. ___ Show C of O
01/23/2008 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… ___ Electrical blanks shall be placed in all open spaces within any electrical panel or box.
01/23/2008 VIOL - FIRE RESIST.RATED CONST JLONGO Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire ___ Replace all lost, broken, or removed tile
01/23/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ___ Service and tag all portable fire exstinguishers ___ Service and tag entire hood system and/or up grade entire system
01/23/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises _____ Clean entire hood system and grease off of roof
01/23/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply, in the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ____ Fix all emergency lighting Located in: Main lobby, above first booth, east wall, mens rest room, both womens rest rooms, above ice cream machine, above salad bar, dry goods store room, dish room, and in bus room. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after _____/____/____. Call Inspector Longo at 791-4502, if you have any further questions. Thank you. Re-inspection passed ________________________________ Joseph P. Longo
01/23/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed… Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. ____ Remove all thumb turn locks on lobby doors ____ Remove key lock on rear exit door in kitchen
02/07/2008 INSP - REINSPECTION JLONGO Correction Required Majority of the violations have been completed. There has been some delays in completion of the hood system. wildcat fire has informed me that they will be done with the hood system by 2/22/08. re-inspection will be set for 2/25/08