Case: T08FR00226

Parcel: 10409002D


Addresses:

4329 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR00226

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/23/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance.
Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

___ Service and tag all portable fire exstinguishers

___ Service and tag entire hood system and/or up grade entire system
01/23/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required 904.11.6.3 Cleaning.
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises

_____ Clean entire hood system and grease off of roof