Case: T08FR00063
Case Details
Entered Date:
01/04/2008
Applicant:
N/A
Description:
Full Inspection
Outstanding Inspections
Case Number: T08FR00063
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag the kitchen hood extinguishing system. #2.The kitchen hood extinguishing system nozzles shall be properly aligned with the cooking equipment. |
01/04/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.5 A class K rated fire extinguisher shall be mounted in the kitchen. |
01/04/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.7 Comply with this code. |
01/04/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.5 Remove the bottom thumb-turn lock from the main entrance/exit door in the dinning area. |
01/04/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.1 Two exit signs shall be posted indicating the direction of the back exit. |
01/04/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 All compressed gas cylinders shall secured to a fixed object with one or more restraints. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00063
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |