Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR00063

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/04/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.5 A class K rated fire extinguisher shall be mounted in the kitchen.
01/04/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 #1.Service and tag the kitchen hood extinguishing system.
#2.The kitchen hood extinguishing system nozzles shall be properly aligned with the cooking equipment.
01/04/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.7 Comply with this code.