Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR02542
Case Details
Entered Date:
12/17/2007
Applicant:
RITA & HOUGHTON LLC
Description:
General Inspection
Outstanding Inspections
Case Number: T07FR02542
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2007 | INSP - FULL | JBEZEL | Correction Required | The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___1. PROBLEM: Extension cord used behind T.V. in dining area TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. REQUIRED CORRECTION: Plug T.V. directly into power outlet or plug power strip directly into outlet. ___2. PROBLEM: Electric panel in kitchen blocked by ladder, mops and brooms etc. TFC REFERENCE: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. REQUIRED CORRECTION: Provide required clearance space from around electrical panel. The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated. Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. |