Case: T07FR02542

Parcel: 141153540

Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T07FR02542

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/17/2007 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Extension cord used behind T.V. in dining area
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with portable appliances.
REQUIRED CORRECTION: Plug T.V. directly into power outlet or plug power strip directly into outlet.

___2. PROBLEM: Electric panel in kitchen blocked by ladder, mops and brooms etc.
TFC REFERENCE: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated working space.
REQUIRED CORRECTION: Provide required clearance space from around electrical panel.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.


Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.