Case: T07FR02352
Case Details
Entered Date:
11/19/2007
Applicant:
GAMMA DELTA HOLDING CORP
Description:
Full Inspection (Fraternity)
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02352
Case Description: INSPECTION
Total Completed Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2007 | VIOL - MEANS OF EGRESS | BCORRALE | Approved | ____Emergency lighting out of service. 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. ***Repair emergency lighting. |
| 11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | ____Mattresses on loft area of room, blocking sprinkler coverage area. (room 10) 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. ***Remove ALL mattresses, storage. |
| 11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | ____Alarm system due for annual test, no tag. ***Have system tested, provide copies of test results to T.F.D. |
| 11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | ____Sprinkler system due for annual testing. **Have sprinkler system tested. Provide copies of test results to T.F.D. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 901.8 Removal of or tampering with equipment. It shall be unlawful for any person to remove, tamper with or otherwise disturb any fire hydrant, fire detection and alarm system, fire suppression system, or other fire appliance required by this code except for the purpose of extinguishing fire, training purposes, recharging or making necessary repairs. |
| 11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | ____Hood system in Kitchen due for testing of suppression system. ***Have system tested immediately. Provide copies of test to T.F.D. |
| 11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | ____Smoke detectors shall be tested, and log sent to T.F.D. ***Test detectors, submit log. |
| 11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | ____Smoke detector missing cover.(Next to room 1) ***Replace cover. |
| 11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Approved | ____Sprinkler head has paint on frangible bulb.(Across room 7) ***Replace sprinkler head. |
| 11/19/2007 | VIOL - PRECAUTION AGAINST FIRE | BCORRALE | Approved | ____Lint buildup in laundry room 316.2 Clothes dryers. Clothes dryers shall be frequently cleaned to maintain the lint trap and mechanical and heating components free from excessive accumulations of lint. ***Clean entire laundry room. |
| 11/19/2007 | INSP - FULL | BCORRALE | Approved | NOTE: Unable to enter chapter room during initial inspection. (No keys at the time) Chapter room will need to be inspected during re-inspection. |
| 11/19/2007 | INSP - FULL | BCORRALE | Approved | On 11-15-07, a fire prevention inspection was conducted at the Sigma Pi house, 1525 E. Drachman St. Please correct the following Tucson Fire Code violations. All references are from the 2006 International Fire Code, with modifications. |
| 03/07/2008 | INSP - REINSPECTION | BCORRALE | Approved | O.K. 3/4. |