Case: T07FR02352

Parcel: 12317201E


Addresses:

1525 E DRACHMAN ST


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR02352

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2008 VIOL - FIRE PROTECTION SYSTEMS Approved O.K. 3/4.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Sprinkler head has paint on frangible bulb.(Across room 7)
***Replace sprinkler head.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Smoke detector missing cover.(Next to room 1)
***Replace cover.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Smoke detectors shall be tested, and log sent to T.F.D.
***Test detectors, submit log.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Hood system in Kitchen due for testing of suppression system.
***Have system tested immediately. Provide copies of test to T.F.D.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Sprinkler system due for annual testing.

**Have sprinkler system tested. Provide copies of test results to T.F.D.
901.6 Inspection, testing and maintenance.
Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

901.8 Removal of or tampering with equipment. It shall be unlawful for any person to remove, tamper with or otherwise disturb any fire hydrant, fire detection and alarm system, fire suppression system, or other fire appliance required by this code except for the purpose of extinguishing fire, training purposes, recharging or making necessary repairs.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Alarm system due for annual test, no tag.
***Have system tested, provide copies of test results to T.F.D.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required ____Mattresses on loft area of room, blocking sprinkler coverage area. (room 10)
901.4 Installation.
Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented
as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance
with applicable standards.
***Remove ALL mattresses, storage.