Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/16/2007

Applicant:

ALPHA PI BLDG CORP

Description:

Full inspection (Sorority)

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02328
Case Description: INSPECTION
Total Completed Inspections - 11
End Date Description Inspector Results Comments
11/16/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Approved ____Light bulb fixture loose, wires exposed. (Guest rooom) 605.1 Abatement of electrical hazards Identified electrical hazards shall be abated. Hazardous conditions in permanent wiring shall be brought to the attention of the code official for enforcement of the ICC Electrical Code. Modified or damaged equipment that constitutes a shock or fire hazard shall not be used. ***Repair lighting fixture.
11/16/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Approved ____Electrical outlet cover missing. (living room) 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. ***Replace outlet cover.
11/16/2007 INSP - FULL BCORRALE Approved On 11/15/07, a fire prevention inspection was conducted at the Delta Gamma House, 1448 E. 1st St. Please correct the following Tucson Fire Code violations. All code references are from the 2006 International Fire Code, with modifications.
11/19/2007 VIOL - MEANS OF EGRESS BCORRALE Approved ____Exit door alarms, and latching systems in need of repair.( sleeping areas, and west stairwell.) 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. 1027.8 Opening force for doors. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a force of not more than 15 pounds (66 N). ***Have door alarms, doors repaired.
11/19/2007 VIOL - MEANS OF EGRESS BCORRALE Approved ____Emergency lighting out of service. 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. ***Repair lighting.
11/19/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved ____Laundry room has lint buildup, clothes behind washers, dryers. 316.2 Clothes dryers. Clothes dryers shall be frequently cleaned to maintain the lint trap and mechanical and heating components free from excessive accumulations of lint. ***Clean entire laundry room.
11/19/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved ____Mirror, Items, boxes in hallway.(ALL hallways, outside room 8) 315.2.2 Means of egress Combustible material shall not be stored in exits or exit enclosures. ***Remove ALL Items from hallways.
11/19/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved ____Storage of combustibles in water heater closets. 315.2.3 Equipment rooms Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. ***Remove all combustible storage from mechanical rooms, closets.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Approved ____Sprinkler system due for annual test. ***Furnish copy of test results to T.F.D.
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Approved ____Fire extinguisher due for testing. (Staff laundry room, Basement) ***Schedule extinguisher inspection.
02/01/2008 COMPLIANCE BCORRALE Approved ALL O.K.