Case: T07FR02328

Parcel: 124040010


Addresses:

1448 E 1ST ST


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR02328

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2008 VIOL - MEANS OF EGRESS Approved ALL O.K.
11/19/2007 VIOL - MEANS OF EGRESS Correction Required ____Emergency lighting out of service.

1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.
***Repair lighting.
11/19/2007 VIOL - MEANS OF EGRESS Correction Required ____Exit door alarms, and latching systems in need of repair.( sleeping areas, and west stairwell.)

1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied.
1027.8 Opening force for doors. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a force of not more than 15 pounds (66 N).
***Have door alarms, doors repaired.