Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR02267
Case Details
Entered Date:
11/08/2007
Applicant:
MC DONALD'S CORPORATION
Description:
F/U on complaint regarding Hood System
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02267
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBEZEL | Approved | Upon further investigation the following code violation for the hood system will need correcting: ___PROBLEM: Pull stations are located on cooking units. TFC: 904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximumof 20 feet (6096 mm) from the kitchen exhaust system. REQUIRED CORRECTION: Have required pull stations installed as per outlined in code. Property Representative Signature:_________________________ Fire Inspector Signature:_________________________ 791-4502 Reinspection date: ___/___/___. |