Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

11/08/2007

Applicant:

MC DONALD'S CORPORATION

Description:

F/U on complaint regarding Hood System

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR02267
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/19/2007 VIOL - FIRE PROTECTION SYSTEMS JBEZEL Approved Upon further investigation the following code violation for the hood system will need correcting: ___PROBLEM: Pull stations are located on cooking units. TFC: 904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximumof 20 feet (6096 mm) from the kitchen exhaust system. REQUIRED CORRECTION: Have required pull stations installed as per outlined in code. Property Representative Signature:_________________________ Fire Inspector Signature:_________________________ 791-4502 Reinspection date: ___/___/___.