Case: T07FR02261
Case Details
Entered Date:
11/08/2007
Applicant:
WEINGARTEN NOSTAT INC
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T07FR02261
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2007 | INSP - FULL | JBURGE | Correction Required | Please correct the following Tucson Fire Code Violations: |
11/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.63 #1.Service and tag the kitchen hood extinguishing system. #2.Service and tag the sprinkler system. #3.Replace the missing FDC inlet covers for the sprinkler system. |
11/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.4 Chain and lock the sprinkler system control valve in the open position. |
11/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Mount the class K portable fire extinguisher located in the kitchen on a hanger. |
11/08/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Repair the emergency lighting unit located in the loading dock for the kitchen. |