Case: T07FR01998
Case Details
Entered Date:
10/08/2007
Applicant:
PARTNERS ON FOURTH INV LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T07FR01998
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1 Post a sign on the liquor room door stating " Fire alarm controll Panel inside". |
10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove the storage from obstructing the electrical service panel located in the liquor room. |
10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 #1.Remove the extension cord used to power the dishwasher located in the bar back room. #2.Remove the 2 extension cords used to power the soda compressors. #3.Remove the extension cord located behind the cooking equipment in the kitchen. #4.Remove the extension cord used to power the fan located by the roll-up door in the kitchen. #5.Remove the yellow extension cord used to power the frige located in the kitchen by the cooking equipment. |
10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 #1.An approved cover shall be placed over the exposed wiring located above the air hocked table. #2.An approved cover shall be placed over the exposed wiring located on the bar back ceiling. |
10/08/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Replace the missing ceiling tile locate in the kitchen. |
10/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and test the fire alarm system. #2.Service and test the commercial cooking fire extinguishing system. |
10/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean and remove all grease accumulation from the kitchen hood system and cooking equipment. |
10/08/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1004.3 Post the occupant load inside the main entrance/exit doorway in a conspicuous place. |
10/08/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 #1.The exit sign located by the VIP bar shall be illuminated. #2.The exit sign located on the north side of the patio shall be illuminated. #3.The exit sign located by the north patio bar shall be illuminated. |
10/08/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Repair the 2 emergency lighting units located above the pool tables. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01998
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |