Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/08/2007

Applicant:

PARTNERS ON FOURTH INV LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T07FR01998
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
10/08/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Post a sign on the liquor room door stating " Fire alarm controll Panel inside".
10/08/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove the storage from obstructing the electrical service panel located in the liquor room.
10/08/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 #1.Remove the extension cord used to power the dishwasher located in the bar back room. #2.Remove the 2 extension cords used to power the soda compressors. #3.Remove the extension cord located behind the cooking equipment in the kitchen. #4.Remove the extension cord used to power the fan located by the roll-up door in the kitchen. #5.Remove the yellow extension cord used to power the frige located in the kitchen by the cooking equipment.
10/08/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 #1.An approved cover shall be placed over the exposed wiring located above the air hocked table. #2.An approved cover shall be placed over the exposed wiring located on the bar back ceiling.
10/08/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace the missing ceiling tile locate in the kitchen.
10/08/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and test the fire alarm system. #2.Service and test the commercial cooking fire extinguishing system.
10/08/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease accumulation from the kitchen hood system and cooking equipment.
10/08/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1004.3 Post the occupant load inside the main entrance/exit doorway in a conspicuous place.
10/08/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 #1.The exit sign located by the VIP bar shall be illuminated. #2.The exit sign located on the north side of the patio shall be illuminated. #3.The exit sign located by the north patio bar shall be illuminated.
10/08/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Repair the 2 emergency lighting units located above the pool tables.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01998
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/29/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.