Case: T07FR01998

Parcel: 11706078A


Addresses:

213 N 4TH AV

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/08/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3 Remove the storage from obstructing the electrical service panel located in the liquor room.
10/08/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 #1.Remove the extension cord used to power the dishwasher located in the bar back room.
#2.Remove the 2 extension cords used to power the soda compressors.
#3.Remove the extension cord located behind the cooking equipment in the kitchen.
#4.Remove the extension cord used to power the fan located by the roll-up door in the kitchen.
#5.Remove the yellow extension cord used to power the frige located in the kitchen by the cooking equipment.
10/08/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6 #1.An approved cover shall be placed over the exposed wiring located above the air hocked table.
#2.An approved cover shall be placed over the exposed wiring located on the bar back ceiling.