Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR01998
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.3 Remove the storage from obstructing the electrical service panel located in the liquor room. | |
10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 #1.Remove the extension cord used to power the dishwasher located in the bar back room. #2.Remove the 2 extension cords used to power the soda compressors. #3.Remove the extension cord located behind the cooking equipment in the kitchen. #4.Remove the extension cord used to power the fan located by the roll-up door in the kitchen. #5.Remove the yellow extension cord used to power the frige located in the kitchen by the cooking equipment. |
|
10/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.6 #1.An approved cover shall be placed over the exposed wiring located above the air hocked table. #2.An approved cover shall be placed over the exposed wiring located on the bar back ceiling. |