Case: T07FR01961
Case Details
Entered Date:
10/03/2007
Applicant:
CENTRO NP HOLDINGS 1 SPE LLC
Description:
Full Fire Inspection.
Outstanding Inspections
Case Number: T07FR01961
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2 Storage shall not be located on or next to the water heater in the janitors closet. |
10/03/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Replace the missing ceiling tile located in the computer room. |
10/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and test the fire alarm system of provide documentation of current annual service and testing. #2.Service and tag the automatic sprinkler system. NOTE:The system side guage is reading 0 psi indicating no water on the system side. Inspect the sprinkler check valve. #3.Remove all dust and grime from the automatic sprinkler system heads, located throughout the building. |
10/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.3.3 Automatic sprinklers shall be installed under both stair cases located in the stock room. |
10/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.6 The portable fire extinguisher located in the window stock room shall not be obstructed from view. |
10/03/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 The exit/entrance doors located by the east side of the building shall have a fully illuminated exit sign. |
10/03/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 #1.Repair the emergency lighting unit located in the employee lunch room. #2.Repair the emergency lighting unit located in the mens restroom. #3.Repair the emergency lighting unit located in the womens restroom. |
10/03/2007 | VIOL - HIGH PILED COMBUSTIBLES | JBURGE | Correction Required | TFC 2305.4 All aisles located in the stock rooms shall have a minimum unobstructed width of 24 inches. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01961
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2007 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |