Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/03/2007

Applicant:

CENTRO NP HOLDINGS 1 SPE LLC

Description:

Full Fire Inspection.

Outstanding Inspections

Case Number: T07FR01961
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
10/03/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Storage shall not be located on or next to the water heater in the janitors closet.
10/03/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace the missing ceiling tile located in the computer room.
10/03/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and test the fire alarm system of provide documentation of current annual service and testing. #2.Service and tag the automatic sprinkler system. NOTE:The system side guage is reading 0 psi indicating no water on the system side. Inspect the sprinkler check valve. #3.Remove all dust and grime from the automatic sprinkler system heads, located throughout the building.
10/03/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.3.3 Automatic sprinklers shall be installed under both stair cases located in the stock room.
10/03/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.6 The portable fire extinguisher located in the window stock room shall not be obstructed from view.
10/03/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 The exit/entrance doors located by the east side of the building shall have a fully illuminated exit sign.
10/03/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 #1.Repair the emergency lighting unit located in the employee lunch room. #2.Repair the emergency lighting unit located in the mens restroom. #3.Repair the emergency lighting unit located in the womens restroom.
10/03/2007 VIOL - HIGH PILED COMBUSTIBLES JBURGE Correction Required TFC 2305.4 All aisles located in the stock rooms shall have a minimum unobstructed width of 24 inches.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01961
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/03/2007 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: