Case: T07FR01961

Parcel: 10509550A


Addresses:

4861 N STONE AV

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
10/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 #1.Service and test the fire alarm system of provide documentation of current annual service and testing.
#2.Service and tag the automatic sprinkler system.
NOTE:The system side guage is reading 0 psi indicating no water on the system side. Inspect the sprinkler check valve.
#3.Remove all dust and grime from the automatic sprinkler system heads, located throughout the building.
10/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.6 The portable fire extinguisher located in the window stock room shall not be obstructed from view.
10/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 903.3.3 Automatic sprinklers shall be installed under both stair cases located in the stock room.