Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01961
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 901.6 #1.Service and test the fire alarm system of provide documentation of current annual service and testing. #2.Service and tag the automatic sprinkler system. NOTE:The system side guage is reading 0 psi indicating no water on the system side. Inspect the sprinkler check valve. #3.Remove all dust and grime from the automatic sprinkler system heads, located throughout the building. |
|
10/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 906.6 The portable fire extinguisher located in the window stock room shall not be obstructed from view. | |
10/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 903.3.3 Automatic sprinklers shall be installed under both stair cases located in the stock room. |