Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/29/2007

Applicant:

K-GAM TRACT C LLC 50% & B TRACT C LLC 15.0506% &

Description:

full inspection

Outstanding Inspections

Case Number: T07FR01705
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/29/2007 INSP - NIGHT FCONTRER Scheduled 2006 IFC- 315.2.1 The display is blocking the sprinkler head. The display shall be 18 inches below the sprinkler head. 2006 IFC- 605.4 Multi plug adapter not complying with the ICC Electrical code shall be prohibited. 2006 IFC-807.1.2 Over the bar area is a grass decoration needs to make it flame proof. (Combustable decoration materials). 2006 IFC-510.1 The sprinkler room shall be labeled RISER ROOM. Firefighters can locate quicker, reduce water damage. 2006 IFC-605.5 Extension cord in the kitchen area, shall not be a substitute for permanent wiring.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01705
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/18/2007 INSP - FULL FCONTRER Approved The grate in the first bay is repaired, no further action needed.