Case: T07FR01705

Parcel: 12801001A


Addresses:

170 S WILMOT RD


Inspection Status: Scheduled

Inspection History: INSP - NIGHT

Case Number - T07FR01705

Inspection Description - INSP - NIGHT

Inspection Status - Scheduled

Date Description Inspector Results Comments
08/29/2007 INSP - NIGHT Scheduled 2006 IFC- 315.2.1 The display is blocking the sprinkler head. The display shall be 18 inches below the sprinkler head.
2006 IFC- 605.4 Multi plug adapter not complying with the ICC Electrical code shall be prohibited.
2006 IFC-807.1.2 Over the bar area is a grass decoration needs to make it flame proof. (Combustable decoration materials).
2006 IFC-510.1 The sprinkler room shall be labeled RISER ROOM. Firefighters can locate quicker, reduce water damage.
2006 IFC-605.5 Extension cord in the kitchen area, shall not be a substitute for permanent wiring.