Case: T07FR01384
Case Details
Entered Date:
07/25/2007
Applicant:
MIKLOFSKY REVOCABLE TRUST
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01384
Case Description: INSPECTION
Total Completed Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | 2006 IFC 1027.3 REPAIR EXIT SIGN BY OFFICE ROOM |
| 08/22/2007 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | 1008.1.8.4 REMOVE SLIDE BOLTS ON RAT ROOM EXIT DOOR REMOVE SLI DE BOLTS ON EXIT DOOR BY OFFICE HALLWAY REMOVE SLIDE BOLTS ON BACK STOCKROOM EXIT DOOR. |
| 08/22/2007 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Approved | 2006 IFC 315.2.1 KEEP AN 18 INCH CLEARANCE FROM SPRINKLER HEAD TO TOP OF BOXES IN STOCK ROOM. |
| 08/22/2007 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Approved | 2006 IFC 315.2 KEEP THE AREA AROUND HOTWATER HEATER CLEAR OF COMBUSTIBLES. |
| 08/22/2007 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Approved | 2006 IFC 703.1 REPLACE MISSING CEILING TILE ABOVE ELECTRICAL PANEL |
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Approved | HARDWIRE ALL TRACK LIGHTING WHERE CORDS PENETRATE THE CEILING. |
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Approved | 2006 IFC 605.5 REMOVE EXTENSION CORD TO REFRIGERATOR IN BREAK ROOM REMOVE EXTENSION COR TO REFRIG IN BACK STOCKROOM |
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Approved | 2006 IFC 605.3 KEEP CLEARANCE OF 36 INCHES AROUND ELECTRICAL PANEL |
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Approved | 2006 IFC 605.1 PLACE BLANKS IN OPEN SLOTS IN ELECTRICAL PANEL IN RAT ROOM. |
| 08/22/2007 | INSP - FULL | MWAINWRI | Approved |