Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR01384
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | 2006 IFC 605.1 PLACE BLANKS IN OPEN SLOTS IN ELECTRICAL PANEL IN RAT ROOM. |
|
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | 2006 IFC 605.3 KEEP CLEARANCE OF 36 INCHES AROUND ELECTRICAL PANEL |
|
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | 2006 IFC 605.5 REMOVE EXTENSION CORD TO REFRIGERATOR IN BREAK ROOM REMOVE EXTENSION COR TO REFRIG IN BACK STOCKROOM |
|
| 08/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | HARDWIRE ALL TRACK LIGHTING WHERE CORDS PENETRATE THE CEILING. |