Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/11/2007

Applicant:

TUCSON HOUSE APARTMENTS LP

Description:

A complaint/Life safety inspection was done by Inspector John Bieg on 7/10/07. R-2.

Outstanding Inspections

Case Number: T07FR01301
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
07/11/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 503.2.1 Cut the tree branches to attain the required verticle clearance (15 ft) at the oracle access point. A re-inspection is scheduled for 7/27/07.
07/11/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 503.4 There shall be no parking or stoping in the required width of any fire apparatus roadway. NOTE: Notify all vendors, tenants and associated traffic of this code requirements.
07/11/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 503.7.1 Post fire lane signs on the north side of the islands, located on the north side of the building. Signs shall face both directions of travel.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01301
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/16/2007 INSP - LIFE SAFETY JBURGE Approved All noted Tucson Fire Code Violations were corrected on 8/16/07.