Case: T07FR01301
Case Details
Entered Date:
07/11/2007
Applicant:
TUCSON HOUSE APARTMENTS LP
Description:
A complaint/Life safety inspection was done by Inspector John Bieg on 7/10/07. R-2.
Outstanding Inspections
Case Number: T07FR01301
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 503.2.1 Cut the tree branches to attain the required verticle clearance (15 ft) at the oracle access point. A re-inspection is scheduled for 7/27/07. |
07/11/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 503.4 There shall be no parking or stoping in the required width of any fire apparatus roadway. NOTE: Notify all vendors, tenants and associated traffic of this code requirements. |
07/11/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 503.7.1 Post fire lane signs on the north side of the islands, located on the north side of the building. Signs shall face both directions of travel. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01301
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2007 | INSP - LIFE SAFETY | JBURGE | Approved | All noted Tucson Fire Code Violations were corrected on 8/16/07. |