Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE SERVICE FEATURES
Case Number - T07FR01301
Inspection Description - VIOL - FIRE SERVICE FEATURES
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2007 | VIOL - FIRE SERVICE FEATURES | Correction Required | TFC 503.4 There shall be no parking or stoping in the required width of any fire apparatus roadway. NOTE: Notify all vendors, tenants and associated traffic of this code requirements. |
|
07/11/2007 | VIOL - FIRE SERVICE FEATURES | Correction Required | TFC 503.7.1 Post fire lane signs on the north side of the islands, located on the north side of the building. Signs shall face both directions of travel. | |
07/11/2007 | VIOL - FIRE SERVICE FEATURES | Correction Required | TFC 503.2.1 Cut the tree branches to attain the required verticle clearance (15 ft) at the oracle access point. A re-inspection is scheduled for 7/27/07. |