Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/05/2007

Applicant:

ST DEMETRIOS GREEK ORTHODOX CHURCH INC

Description:

A life safety inspection was done by inspector John Bieg on 7/3/07. A-3/Church.

Outstanding Inspections

Case Number: T07FR01260
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
07/05/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.2 There shall be no storage under the exterior stairway.
07/05/2007 VIOL - INT.FINISH, DEC. MATL'S JBURGE Correction Required TFC 803.1.3 Remove all items from blocking the northeast exit door in the church. A re-inspection is scheduled for 7/17/07.
07/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag the hood system located in the kitchen.
07/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Remove the surface bolt from the egress door in the nursery.
07/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.3 #1.The west exit sign located in the church shall be illuminated. #2.The east exit sign located in the church shall be fully illuminated. #3.The northeast exit sign in the hall shall be fully illuminated. #4.The northwest exit sign in the hall shall be fully illuminated. #5.The exit sign by the ramp exit in the church shall be fully illuminated.
07/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 #1.The emergency lighting unit located above the south exit in the hall shall be repaired. #2.The northeast and northwest emergency lighting units located above the exit doors in the hall shall be repaired.
07/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove the thumb turn lock from the west exit door in the church.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01260
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/30/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 7/27/07.