Case: T07FR01260

Parcel: 113043470

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR01260

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/05/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1027.6 Remove the thumb turn lock from the west exit door in the church.
07/05/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.4 Remove the surface bolt from the egress door in the nursery.
07/05/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1026.5 #1.The emergency lighting unit located above the south exit in the hall shall be repaired.
#2.The northeast and northwest emergency lighting units located above the exit doors in the hall shall be repaired.
07/05/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1026.3 #1.The west exit sign located in the church shall be illuminated.
#2.The east exit sign located in the church shall be fully illuminated.
#3.The northeast exit sign in the hall shall be fully illuminated.
#4.The northwest exit sign in the hall shall be fully illuminated.
#5.The exit sign by the ramp exit in the church shall be fully illuminated.