Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/19/2007

Applicant:

SALKIN AVRAM TR OF LEE KIVEL TRUST 1/2 &

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T07FR01167
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
07/03/2007 INSP - REINSPECTION NSPRENGE Continued Per IFC 904.11.6.4 ( added to initial inspection today ) advised business owner that the extinguishing system is a dry chemical system and needs to be inspected by professional to determine if system is adequate or if a new system ( wet chemical ) needs to be installed.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01167
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
07/03/2007 VIOL - MEANS OF EGRESS NSPRENGE Approved All corrections made.
07/03/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Approved corrected.
07/17/2007 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Approved System is not a UL 300 wet system, but did pass the inspection with Independent Fire and Safety. Gas shut off, and system operated effectively. Owners were advised they will need to switch to a UL 300 wet system when the current system no longer passes its inspections.
07/17/2007 VIOL - COMPRESSED GASES NSPRENGE Approved cylinders are secured properly. Approved.