Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/01/2007

Applicant:

AGARWAL RAJ & DARSHAN

Description:

lpg

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01062
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/01/2007 INSP - AST/UST CFUNKE Approved 3807.1 Safety devices. Safety devices on LPG containers, equipment and systems, shall not be tampered with or made ineffective. LPG containers are required to have current certification according to manufacturer's specifications. - The fusible link on the thermal accuated device shall have a melting point of no more than 250 degrees F.
06/14/2007 INSP - REINSPECTION JLANGEJA Approved Servi Gas was on site to de-fuel 1000 gal. propane tank in order to replace a thermal actuated valve below the liquid level. Fuel that could not be pumped out was burned off until the pressure was gone. They will recontact when they are ready to put tank back in service.