Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/29/2007

Applicant:

FRONTIER VILLAGE LLC 90.33%

Description:

Full Fire Prevention Inspection (FPI) conducted 5/25/07

Outstanding Inspections

Case Number: T07FR01020
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required Open space in electrical panel: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _____ Place an approved "blank" in the space.
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 2003 requires that all relocatable power taps be grounded, have overcurrent protection, and be plugged directly into a permanent electrical outlet. TFC 2003 prohibits flexable electric cords from being extended through ceilings, thorugh walls, doors or windows, and from being run under carpets. TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove noncomplying devices (extension cords, multi-plug adaptors and relocatable power taps without 3-conductor grounding and overcurrent protection). _____ Plug approved relocatable power taps directly into permanent outlets. _____ Remove flexible electric cords from ceiling tiles.
05/29/2007 VIOL - COMPRESSED GASES DGREENLE Correction Required Compressed gas cylinders not secured: TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment... _____ Secure all gas cylinder, whether full or not, to avoid accidental dislodgment, in an approved manner.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01020
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/29/2007 INSP - FULL DGREENLE Approved A copy of the Certificate of Occupancy and the occupancy load card are on file with TFD Prevention. They shall also be posted on the premesis. Sprinkler system inspected 5/1/07. Keep a copy of sprinkler inspection reports on the premesis for 3 years. Hood and kitchen extinguisher system inspection completed 5/07. TFC 2003 requires commercial hoods be inspected every 6 months and that records be kept of regular cleaning. GREAT JOB on your hood cleaning and inspection. Your commitment to fire safety is appreciated!
06/14/2007 COMPL - REINSPECTION DGREENLE Approved