Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR01020
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Open space in electrical panel: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _____ Place an approved "blank" in the space. |
|
05/29/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 2003 requires that all relocatable power taps be grounded, have overcurrent protection, and be plugged directly into a permanent electrical outlet. TFC 2003 prohibits flexable electric cords from being extended through ceilings, thorugh walls, doors or windows, and from being run under carpets. TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove noncomplying devices (extension cords, multi-plug adaptors and relocatable power taps without 3-conductor grounding and overcurrent protection). _____ Plug approved relocatable power taps directly into permanent outlets. _____ Remove flexible electric cords from ceiling tiles. |