Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/21/2007

Applicant:

RMT VENTURES INC

Description:

Full fire inspection done by Inspector John Bieg on 5/21/07. "S-1" / Foam, fabric storage and sewing.

Outstanding Inspections

Case Number: T07FR00982
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
05/21/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Storage shall be maintained at least 2 feet from the ceiling throughout the building, including storage sheds.
05/21/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1. Remove the extension cords that are running through the ceiling to the sewing machine. A re-inspection is scheduled for 6/4/07.
05/21/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1. The light switches located in the office shall have an approved cover.
05/21/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Maintenance. The required fire-resistance rating offire-resistance-rated construction (including walls, fire stops,shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replacedwhen damaged, altered, breached or penetrated. 1. Repair the holes in the ceiling located in the upstairs storage room.
05/21/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Service and tag all fire extinguishers.
05/21/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1. Remove the double keyed deadbolt from the east egress door and security gate. { Replace with thumb turn locks.} 2.Remove the double keyed deadbolt from the north egress door and security gate. { Replace with thumb turn lock.}
05/21/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.2 A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIDE. 1. The west exit door and security gate shall meet the above requirements.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00982
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/25/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 7/25/07.