Case: T07FR00982
Case Details
Entered Date:
05/21/2007
Applicant:
RMT VENTURES INC
Description:
Full fire inspection done by Inspector John Bieg on 5/21/07. "S-1" / Foam, fabric storage and sewing.
Outstanding Inspections
Case Number: T07FR00982
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Storage shall be maintained at least 2 feet from the ceiling throughout the building, including storage sheds. |
05/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1. Remove the extension cords that are running through the ceiling to the sewing machine. A re-inspection is scheduled for 6/4/07. |
05/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1. The light switches located in the office shall have an approved cover. |
05/21/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating offire-resistance-rated construction (including walls, fire stops,shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replacedwhen damaged, altered, breached or penetrated. 1. Repair the holes in the ceiling located in the upstairs storage room. |
05/21/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Service and tag all fire extinguishers. |
05/21/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1. Remove the double keyed deadbolt from the east egress door and security gate. { Replace with thumb turn locks.} 2.Remove the double keyed deadbolt from the north egress door and security gate. { Replace with thumb turn lock.} |
05/21/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.2 A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIDE. 1. The west exit door and security gate shall meet the above requirements. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00982
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 7/25/07. |