Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00982
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1. Remove the double keyed deadbolt from the east egress door and security gate. { Replace with thumb turn locks.} 2.Remove the double keyed deadbolt from the north egress door and security gate. { Replace with thumb turn lock.} |
|
05/21/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8.2 A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIDE. 1. The west exit door and security gate shall meet the above requirements. |