Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/11/2007

Applicant:

USRP FUNDING 2001-A LP

Description:

Full fire inspection done by Inspector John Bieg on 5/11/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR00939
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
05/11/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
05/11/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Submit plans for hood system upgrade to a UL 300 wet chemical extinguishing system. NOTE: An appeal has been approved by the fire Code official Dan Uthe, to extend the compliance date to 10/9/07. A re-inspection is scheduled for 5/25/07.
05/11/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.5 There shall be a class K fire extinguisher within a 30 foot travel distance of commercial-type cooking equipment. NOTE: An appeal has been approved by the fire Code official Dan Uthe, to extend the compliance date to 10/9/07.
05/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 #1. Remove the double keyed deadbolt from the south exit door. {Replace with a thumb turn deadbolt.} #2. The exit gate located in the outside dinning area shall be readily openable from the egress side without the use of a key.
05/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 The exit with double doors in the dinning area shall comply with this code.
05/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 The exit gate located in the outside dinning area shall have an illuminated exit sign.
05/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove the thumb turn lock from the exit door in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00939
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/09/2007 INSP - FULL JBURGE Approved All noted Tucson Fire code violations were corrected on 10-9-07.