Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR00939
Case Details
Entered Date:
05/11/2007
Applicant:
USRP FUNDING 2001-A LP
Description:
Full fire inspection done by Inspector John Bieg on 5/11/07. "A-2" / Restaurant.
Outstanding Inspections
Case Number: T07FR00939
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Comply with this code. |
05/11/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Submit plans for hood system upgrade to a UL 300 wet chemical extinguishing system. NOTE: An appeal has been approved by the fire Code official Dan Uthe, to extend the compliance date to 10/9/07. A re-inspection is scheduled for 5/25/07. |
05/11/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.5 There shall be a class K fire extinguisher within a 30 foot travel distance of commercial-type cooking equipment. NOTE: An appeal has been approved by the fire Code official Dan Uthe, to extend the compliance date to 10/9/07. |
05/11/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 #1. Remove the double keyed deadbolt from the south exit door. {Replace with a thumb turn deadbolt.} #2. The exit gate located in the outside dinning area shall be readily openable from the egress side without the use of a key. |
05/11/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 The exit with double doors in the dinning area shall comply with this code. |
05/11/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.1 The exit gate located in the outside dinning area shall have an illuminated exit sign. |
05/11/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.6 Remove the thumb turn lock from the exit door in the kitchen. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00939
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire code violations were corrected on 10-9-07. |