Case: T07FR00939

Parcel: 116191630

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00939

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/11/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.5 There shall be a class K fire extinguisher within a 30 foot travel distance of commercial-type cooking equipment.
NOTE: An appeal has been approved by the fire Code official Dan Uthe, to extend the compliance date to 10/9/07.
05/11/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Submit plans for hood system upgrade to a UL 300 wet chemical extinguishing system.
NOTE: An appeal has been approved by the fire Code official Dan Uthe, to extend the compliance date to 10/9/07.

A re-inspection is scheduled for 5/25/07.