Applicant:

BROADWAY POWER CENTER GROUP LLC

Description:

Full Inspection conducted 4/25

Outstanding Inspections

Case Number: T07FR00875
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____ The hood exhaust and extinguishing systems shall be inspected and tagged. NOTE: Petition to have hood extinguishing system removed granted by Chief Uthe 6/25/07. NO COOKIG INVOLVING THE USE OF GREASE OR OIL, OR PROCESSES THAT PRODUCE GREASE-LADEN VAPORS SHALL BE ALLOWED. VIOLATION OF THIS ALLOWANCE SHALL RESULT IN IMMEDIATE CEASSATION OF OPERATIONS UNTIL AN APPROVED SYSTEM IS IN PLACE.
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.6 - Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____ Replace cover for electrical outlet.
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 901.6 - Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ 1. Extinguishers shall be inspected and tagged in accordance with this code.
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. _____ A "40B-C" or "K" class extinguisher shall be installed according to this code.
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
05/29/2007 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1008.1 - Doors. Means of egress doors shall meet the requirements of this section... Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section Double keyed lock on door: TFC 1008.1.8 - Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. TFC 1008.1.8.3 - Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ The front door shall comply with the Tucson Fire Code. _____ The rear door shall comply with the Tucson Fire Code.
05/29/2007 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1026.3 - Exit sign illumination. Exit signs shall be internally or externally illuminated. _____ Fix light in exit sign.
05/29/2007 VIOL - COMPRESSED GASES DGREENLE Correction Required TFC 3003.3 - Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment... _____ Secure gas cylinder to avoid accidental dislodgment, in an approved manner.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00875
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/03/2007 INSP - FULL DGREENLE Approved Sprinkler System inspected 2/07, Keep a record of all sprinkler inspections in your files for 3 years.