Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T07FR00757
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/20/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2003 IFC 605.1 REPLACE MISSING PLATE COVER ON OUTLET IN OFFICE.
04/20/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2003 IFC 605.3 KEEP AT LEAST 36 INCH WORKING SPACE CLEAR IN FRONT OF ELECTRICAL PANEL.
04/20/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2003 IFC 605.4 REPLACE EXTENSION CORD WITH POWER STRIP IN BIRD ROOM. REPLACE UNPROTECTED CUBE WITH APPROVED POWER STRIP IN BIRD ROOM.
04/20/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2003 IFC 605.5 REPLACE EXTENSION CORD BEING USED TO POWER FREZZER IN BIRD ROOM. NEEDS APPROVED OUTLET.
04/20/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2003 IFC 1008.1.8.4 REMOVE SLIDE BOLTS ON RIGHT SIDE OF DOUBLE DOOR IN BACK ROOM. ( RECEIVING AREA)
04/20/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2003 IFC 1008.1.9 REPAIR EMERGENCY EXIT DOOR SO IT WILL OPEN READILY AND WITH A MAXIMUM FORCE OF 15 POUNDS ON TAHE NORTH SIDE IN MIDDLE OF STORE.
04/20/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2003 IFC 1026.3 REPAIR EXTI SIGN ON NORTH SIDE MIDDLE OF STORE.