Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00757
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/20/2007 | VIOL - MEANS OF EGRESS | Violation | 2003 IFC 1008.1.8.4 REMOVE SLIDE BOLTS ON RIGHT SIDE OF DOUBLE DOOR IN BACK ROOM. ( RECEIVING AREA) |
|
04/20/2007 | VIOL - MEANS OF EGRESS | Violation | 2003 IFC 1026.3 REPAIR EXTI SIGN ON NORTH SIDE MIDDLE OF STORE. |
|
04/20/2007 | VIOL - MEANS OF EGRESS | Violation | 2003 IFC 1008.1.9 REPAIR EMERGENCY EXIT DOOR SO IT WILL OPEN READILY AND WITH A MAXIMUM FORCE OF 15 POUNDS ON TAHE NORTH SIDE IN MIDDLE OF STORE. |