Case: T07FR00732
Case Details
Entered Date:
04/17/2007
Applicant:
LEON LLC
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR00732
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
04/17/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.5 Extension cords. Extension cords shall not be a substitute for permanent wiring. Remove extension cord attached to food warmer in kitchen. |
04/17/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.6 Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Provide an approved cover for the open wiring on your hot water heater in kitchen area. |
04/17/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1006.1 Illumination required. The means of egress shall be illuminated at all times the building space served by the means of egress is occupied. Cause your emergency lighting in kitchen area to work. a performance. It is not the intent of the exception to require a fire alarm system, but to require a connection |
04/17/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1008.1.8.3 Locks and latches shall be permitted where a readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. Place this sign above your front entrance where there is a key cylinder only. |
04/17/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1011.5.3 Exit signs shall be illuminated at all times. Cause your back up power to operate properly and illuminate the exit sign over the rear kitchen entrance. |
04/17/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1027.2 Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions. Remove boxes blocking kitchen exit near hotwater heater and maintain free of obstructions. |
04/17/2007 | VIOL - COMPRESSED GASES | NSPRENGE | Violation | 3003.3.3 Compressed gas cylinders shall be secured to prevent falling caused by contact, vibration or seismic activity. Properly secure your three gas cylinders in the kitchen area. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00732
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2007 | COMPL - REINSPECTION | NSPRENGE | Approved | All noted hazards and code violations have been abated. |