Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T07FR00732
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/17/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.5 Extension cords. Extension cords shall not be a substitute for permanent wiring. Remove extension cord attached to food warmer in kitchen.
04/17/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.6 Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Provide an approved cover for the open wiring on your hot water heater in kitchen area.
04/17/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1006.1 Illumination required. The means of egress shall be illuminated at all times the building space served by the means of egress is occupied. Cause your emergency lighting in kitchen area to work. a performance. It is not the intent of the exception to require a fire alarm system, but to require a connection
04/17/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1008.1.8.3 Locks and latches shall be permitted where a readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. Place this sign above your front entrance where there is a key cylinder only.
04/17/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1011.5.3 Exit signs shall be illuminated at all times. Cause your back up power to operate properly and illuminate the exit sign over the rear kitchen entrance.
04/17/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1027.2 Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions. Remove boxes blocking kitchen exit near hotwater heater and maintain free of obstructions.
04/17/2007 VIOL - COMPRESSED GASES NSPRENGE Violation 3003.3.3 Compressed gas cylinders shall be secured to prevent falling caused by contact, vibration or seismic activity. Properly secure your three gas cylinders in the kitchen area.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00732
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/23/2007 COMPL - REINSPECTION NSPRENGE Approved All noted hazards and code violations have been abated.