Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00732
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/17/2007 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8.3 Locks and latches shall be permitted where a readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. Place this sign above your front entrance where there is a key cylinder only. |
|
04/17/2007 | VIOL - MEANS OF EGRESS | Violation | 1006.1 Illumination required. The means of egress shall be illuminated at all times the building space served by the means of egress is occupied. Cause your emergency lighting in kitchen area to work. a performance. It is not the intent of the exception to require a fire alarm system, but to require a connection |
|
04/17/2007 | VIOL - MEANS OF EGRESS | Violation | 1011.5.3 Exit signs shall be illuminated at all times. Cause your back up power to operate properly and illuminate the exit sign over the rear kitchen entrance. | |
04/17/2007 | VIOL - MEANS OF EGRESS | Violation | 1027.2 Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions. Remove boxes blocking kitchen exit near hotwater heater and maintain free of obstructions. |