Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR00392
Case Details
Entered Date:
02/26/2007
Applicant:
MOUNTAIN OYSTER CLUB INC
Description:
FPI with SIP information generated by Request for Inspector #2487 (leach/07) T07FR00390
Outstanding Inspections
Case Number: T07FR00392
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2007 | INSP - FULL | DGREENLE | Correction Required | 1997 Uniform Administrative Code 309.5 Posting.The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. _____ A current Certificate of Occupancy (C of O) shall be provided upon re-inspection. If not available, manager will be in the process of acquiring it. This address shall be listed with Pima County Addressing before a C of O will be issued. Occupancy is eligible for TFD's "Self-Inspection Program" |
03/02/2007 | VIOL - FIRE SERVICE FEATURES | DGREENLE | Correction Required | _____ TFC 505.1 New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____ Main intrance to Suite #120 shall be plainly identified once inside the courtyard. Manager received a copy of the "Pima County Address Display Requirements" flyer. |
03/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.1 - Identified electrical hazards shall be abated. _____ Electrical outlet located near sink shall be protected with "Ground Fault Circuit Interruption." TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. _____ Replace extension for refridgerator with approved power strip. TFC - 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____ Junction box below sink shall have approved cover. |
03/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All portable extinguishers shall be tested and tagged. |
03/02/2007 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting TFC 1008.1 - ...Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side. _____ Remove double-keyed deadbolt from rear door. _____ Clearly and legibly sign the 3 sealed doorways in storage area "NOT AN EXIT" TFC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove double-keyed deadbolt from northwest door. _____ Remove double keyed deadbolt from northeast door in storage area. _____ Repair door between storage area and northeast exit to meet the standards of of the code. TFC 1008.1.8.3 - Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: ... 2 (Group M) the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Provide approved signage for front door. TFC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. _____ Place exit signs in an approved manner over the egress doors in the storage area. TFC 1026.3 - Exit signs shall be internally or externally illuminated. _____ Fix light or battery back-up in exit signs. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00392
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2007 | COMPL - REINSPECTION | DGREENLE | Approved | Compliance on all matters. Addressing has been changed and a new C of O is being issued. Occupancy is turned over to Self-Inspection Program. |