Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00392

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/02/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 - Identified electrical hazards shall be abated.

_____ Electrical outlet located near sink shall be protected with "Ground Fault Circuit Interruption."

TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed.
TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring.

_____ Replace extension for refridgerator with approved power strip.

TFC - 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

_____ Junction box below sink shall have approved cover.