Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00392
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.1 - Identified electrical hazards shall be abated. _____ Electrical outlet located near sink shall be protected with "Ground Fault Circuit Interruption." TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. _____ Replace extension for refridgerator with approved power strip. TFC - 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____ Junction box below sink shall have approved cover. |