Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/21/2007

Applicant:

TUCSON SCHOOL DISTRICT NO 1

Description:

FPI 1/23/07 - Greenleaf/Grijalva

Outstanding Inspections

Case Number: T07FR00370
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
02/21/2007 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required TFC 315.2.3 - Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____ Remove storage from electrical service room.
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. _____ Replace with approved power strip, Primary Kiva, Library Kiva
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _____ Place an approved "blank" in the space.
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel in an approved manner.
02/21/2007 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1026.3 - Exit sign illumination. Exit signs shall be internally or externally illuminated. _____ Several exit signs not illuminated by emergency power shall be repaired.
02/21/2007 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Emergency lighting not working shall be repared.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00370
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
04/10/2007 COMPLIANCE DGREENLE Approved
04/10/2007 INSP - FULL DGREENLE Approved