Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00370

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring.

_____ Replace with approved power strip, Primary Kiva, Library Kiva
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____ Place an approved "blank" in the space.
02/21/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear area in front of electrical panel in an approved manner.