Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/13/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-13-07.

Outstanding Inspections

Case Number: T07FR00325
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
02/13/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The exit sign over the main entrance shall be illuminated. #2. The exit sign in the storage room shall be illuminated. {Back-up power}.
02/13/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 The emergency lighting in the back room shall have emergency back up power. A re-inspection is scheduled for 2-27-07.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00325
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/02/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 2-28-07. Inspector John Bieg.