Case: T07FR00325
Case Details
Entered Date:
02/13/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-13-07.
Outstanding Inspections
Case Number: T07FR00325
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 #1. The exit sign over the main entrance shall be illuminated. #2. The exit sign in the storage room shall be illuminated. {Back-up power}. |
02/13/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 The emergency lighting in the back room shall have emergency back up power. A re-inspection is scheduled for 2-27-07. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00325
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-28-07. Inspector John Bieg. |