Case: T07FR00325

Parcel: 10511061R


Addresses:

4500 N ORACLE RD

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
02/13/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1011.2 #1. The exit sign over the main entrance shall be illuminated.
#2. The exit sign in the storage room shall be illuminated. {Back-up power}.
02/13/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1026.5 The emergency lighting in the back room shall have emergency back up power.

A re-inspection is scheduled for 2-27-07.