Case: T07FR00162
Case Details
Entered Date:
01/18/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 1-18-07.
Outstanding Inspections
Case Number: T07FR00162
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Remove storage from blocking electrical service equipment. In back stock room. Call me if you have any questions at 791-4014, Ext 122. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00162
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | INSP - FULL | JBURGE | Approved | All Tucson Fire Code violations were corrected on 2-2-07. Inspector John Bieg. |