Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Remove storage from blocking electrical service equipment. In back stock room. Call me if you have any questions at 791-4014, Ext 122. |